The RAYCHEM NGC-20 is a field-mounted electronic temperature control system providing local control and central monitoring capabilities for industrial heat-tracing applications.
The RAYCHEM NGC-20 is an advanced field-mountable electronic temperature control system providing local control and central monitoring capabilities for industrial heat-tracing applications. A true “Smart Thermostat”. Compared to centralised control, the RAYCHEM NGC-20 system can significantly reduce costs without compromising safety and reliability. Approved for hazardous areas, the RAYCHEM NGC-20 is also available with an integrated intelligent safety temperature limiter (SIL 2 device).
Temperatures, earth leakage and operating currents as wells other crucial data associated with heat-tracing circuit integrity is constantly monitored and reported. Both monitoring and configuration of the RAYCHEM NGC-20 can be achieved remotely via the RAYCHEM User Interface Terminal (UIT) and/or by using RAYCHEM Supervisory software application. A hand-held wireless device is also available to enable the system to be configured and monitored in the field without opening the control unit.
Technische Spezifikationen
| Temperature range control unit | –80°C to +700°C in steps of 1K |
| Temperature range limiter | –60°C to +599°C in steps of 1K |
| Ambient operating temperature | –40°C to +56°C |
| Storage temperature | –55°C to +80°C |
Entries
- 3 x M25
- 1 x M25 gland Ø 8 – 17 mm: power IN / heating cable out
- 1 x M25 stopping plug: daisy chaining of power
- 1 x M25 rain plug: daisy chaining of power
- 3 x M20 Digital communication IN / OUT and alarm (all with stopping plugs)
- 2 X M16 Temperature sensor(s) 1 with stopping plug one with rain plug
|
| Power supply & own power consumption | 100 Vac to 254 Vac +/-10 % 50/60 Hz 20 VA max |
| Alarm output relay Contact | rated 250 Vac / 3 A |
| Temperature sensors | 100 Ω platinum, 3-wire |
| Quantity | Two RTD inputs for the control unit
One independent temperature input for the safety limiter (NGC-20-CL-E). |
| Physical network | RS-485 and Bluetooth Class 1 |
| Measurement Load Current | 0.3 A to 30 A |
| Measurement Ground-fault current | 10 mA to 250 mA |